Designing A Wood Railing
With Cable As An In-Fill
|
Overview
There are eight considerations in
designing a railing with cable in-fill:
1. Construction and location of your end posts;
2. Configuration of any corners in your design;
3. Location of intermediate posts;
4. Location of additional cable supports;
5. Cable diameter to use;
6. Spacing of cables on your end post;
7. Whether to cut cables and put fittings on in the
field or use factory cut and swaged cables;
8. Selection of appropriate hardware.
We will address each of these considerations in
order.
1. Construction and location of
your end (terminating) posts.
An end post is a post to which
terminating cable ends are attached with tensioning
or non-tensioning hardware. Considerable tension is
applied to the end posts, when the cable is properly
tensioned. A substantial end post is necessary, to
prevent the end post from bending, which will cause
the cables to sag. In wood, a minimum 4x4 (3-1/2 ”
square) end post is required. End posts must be
securely fastened to the deck or other surface, to
prevent the post from coming loose with the forces
applied through the tensioned cables.
Support members between end posts
are also necessary. In wood, we recommend support
members running between posts, such as a 2x4 secured
to the inside of each post, so you are not relying
on the shear strength of the nails or screws to
support the tension applied to the end post.
 |
2. Configuration of any
corners in your design.
At corners or turns of more than
approximately 45 degrees, it is best to terminate
your runs in each direction with an end post
(minimum of a nominal 4x4). The following
illustrations demonstrate how this is done.

A corner may be
designed using two posts on the corner and running
the cables between the posts as illustrated below.
There must be a tensioner on both ends.

 |
|
Page 1
4/1/07 |
 |
|
A stainless steel flat bar (cable
support) with holes for the cable to pass through is mounted
on each surface where the cable enters or exits the post at
an angle, to prevent the cable from biting into the wood
when it is tensioned.
Cable supports are available from the factory (see the Wood
Accessories section of this publication for order
information). We do not recommend using this type of corner
post configuration on more than one corner between any
two-end posts (with tensioning hardware). When using this
configuration, you will need tensioning hardware on both
ends of the run, and you will need to tension the cables
from both ends.
On a turn of less than approximately 45
degrees, you can run your cables through a single post, but
you will still need to use a cable support where the cable
enters or exits the post at an angle, to prevent the cable
from biting into the wood when it is tensioned.
See No. 8. Selection of appropriate
hardware below for other hardware combinations that can be
used on corner posts.
3. Location of intermediate posts.
Intermediate posts (or mid-posts) are
placed between end posts. An intermediate post runs from the
top rail to the lower mounting surface and is a structural
element.
Intermediate posts should be placed at
intervals between end or corner posts as frequently as
necessary to meet building code requirements. An engineer or
design professional should be engaged, if you are unable to
otherwise determine intermediate post spacing.
Cable is strung through holes drilled in
the intermediate posts, so intermediate posts also become
supports for the cable between end posts.
With cable spaced vertically on centers
as recommended below (see No. 6 Spacing of cables on your
end post), we recommend that the cable be supported in some
manner no more than every 42” along its run. The support can
be provided by an intermediate post or it can be something
thinner such as a 2x4 or a thin steel cable brace (see No. 4
Location of additional cable supports below).
4. Location of additional cable supports.
Regardless of the amount of tension you
apply to the cables, there will be some flex in the cable
when it is installed.
 |
When the cables are spaced vertically on
your end post as we recommend below (see No. 6 Spacing of
cables on your end post), we recommend that the cable be
supported in some manner no more than every 42” along its
run, to meet code requirements that a 4” sphere cannot pass
through the cables.

As indicated above, this support can be
provided with intermediate posts or a lighter material
acting as a cable brace. As with an intermediate post, a
cable brace also runs between the top rail and the lower
mounting surface, but its purpose is only to support the
cable. It is not intended to be an element providing
structural support to the railing.
Cable braces can be much thinner and,
therefore, less obtrusive than posts, as their primary
purpose is only to support the cable.
A ¼”x1” steel flat bar, usually stainless
steel, with holes drilled for the cables to pass through
makes an excellent cable brace. Flat bar cable braces are
available from the factory (see the Wood Accessories section
of this publication for order information).
5. Cable diameter to
use.
It is important to use 1x19 construction
cable as a railing in-fill, because it is attractive, smooth
to the touch, and designed to support loads in tension with
minimal stretch.
The individual wires in 1x19 construction
cable are much larger than those used in more flexible
constructions. This makes the cable less prone to damage
from abuse, and it is also the reason why strand does not
stretch as much as other constructions.

 |
|
Page 2
4/1/07
A print-friendly version is also available (PDF Format)
|
 |
|
You will want to specify type 316
stainless steel, because it is the most corrosion resistant
commercially available alloy used in manufacturing cable.
Ultra-tec® hardware is made from type 316 stainless steel,
so no material compatibility issues will arise when you use
type 316 stainless steel cable with Ultra-tec® hardware.
It is also important to use at least a
3/16” diameter cable. Problems have been experienced with
damage from abuse when 1/8” diameter cable has been used.
Following are minimum breaking strengths for type 316
stainless steel cable.

As the chart above illustrates, for a
small increase in size (and cost) you can more than double
the strength of your in-fill and ensure that damage from
abuse is not an issue with your railing.
Everything considered, 3/16” diameter
1x19 construction type 316 stainless steel cable is usually
the best choice for most railing applications.
6. Spacing of cables on your end post.
Even though you use 1x19 construction
cable and the cables are properly tensioned on a strong end
post, there will be some flex in the cable when a load is
applied.
The spacing of the cable on the end posts
works together with the distance between points where the
cable is supported, to minimize cable flex. The closer
together the cables are spaced on the end posts, the longer
the distance can be between cable support points. The
reverse is also true.
Weighing the wish to use as few cables as
necessary with the need to minimize cable flex, we recommend
maximum vertical spacing of the cables on your end posts so
there is no more than a 3” free opening between cables. For
example, if you are using 3/16” cable, you should mount your
cables on the end posts on maximum 3-3/16” centers.

 |
7. Whether to cut cables and put fittings
on in the field or use factory cut cables.
There are three choices to consider for
attaching fittings to the cables. Cables can be: 1) cut at
the job site and the fittings attached using swageless
fittings; 2) cut at the job site and swaged on the cables
using equipment and tools rented or purchased from the
factory or a distributor; or
3) supplied by the factory or a distributor cut to length
with the fittings attached, ready to install.
Swageless Fittings
Swageless fittings are installed by hand
in the field. No special equipment is needed, except cable
cutters. (As with any method of installing, we also
recommend that you use special cable gripping pliers to keep
the cable from turning when you tighten the fittings to
tension the cable. Cable cutters and cable gripping pliers
can be provided at a low cost by the factory and some
distributors).
The first advantage is that the holes the
cables pass through in your intermediate posts do not have
to be any larger than is necessary for just the bare cable
to pass through. If you have fittings already attached to
both ends of the cable, your intermediate post holes must be
at least as large as the diameter of the smallest fitting
attached to the cable. The difference between the hole and
cable diameters will be 1/16” or more, which will cause more
cable deflection than the tighter fit obtained if the
fittings are swaged on site.
The second advantage is that there is no
need to provide accurate measurements to a second party who
is doing the cutting and swaging of the cables. This
eliminates the possibility for misinterpreting your
dimensions. In the field, the cables are cut to a slightly
longer length than necessary and one end fitting is attached
to the cable and then attached to an end post. The cable is
then strung through the railing frame. The bare end is
pulled tight at the opposite end post and marked with a
permanent marker for cutting. The second end fitting is
attached to the cable. The cable is tensioned, and you are
done. You do not have to wait for someone else to make the
cables and ship them to you and take the chance that some of
them may not be cut correctly. Most importantly, you are in
control of when the cables are done.
Field Swaging
Field swaging offers an advantage that
you do not have in using swageless fittings, in that your
choice of fittings is unlimited when you field swage. Field
swaging requires the use of a swaging kit and an air
compressor (see our catalog or installation guide for
compressor specifications) to attach the fittings to the
cables.
 |
Page 3
4/1/07 |
 |
|
Complete instructions are included with
all orders. All of the equipment necessary is available for
purchase or rental from the factory and through some
distributors.
Factory Swaging
If the cables are cut and the fittings swaged by us, you do
not need to use special equipment.
There is a charge for factory cutting and
swaging, but for smaller jobs the cost will be less than
renting the equipment required to field swage the cables.
Some Ultra-tec® hardware is designed to
pass through holes in your intermediate posts that are
drilled as little as 1/16” more than the diameter of the
cable, when both ends are swaged by us. You will find these
fittings outlined in the
following section.
Where the cable will not pass through any
intermediate posts, you can order factory cut and swaged
cables using any hardware. You are not limited as to the
fittings you can use.
If you can use our Push-Lock™ fitting on
one end of your cable, we can supply your cable with one of
our tensioning devices (see 8b below) on one end and only
bare cable on the other end to which the Push-Lock™ fitting
will be attached to the cable by hand. The advantage is that
you need to drill your intermediate post holes only large
enough for the cable to pass through.
8. Selection of appropriate hardware.
In selecting hardware, you will need to consider: a) whether
you want to field cut and swage the cables, have them
factory cut and swaged, or use swageless fittings (see No. 7
Swageless Fittings); b) hardware preferences for end posts;
c) how you wish to configure your corners (if applicable);
d) hardware used for stairs or severe slopes.
a) Field cut and swage, factory cut and
swage, or swageless fittings on the cables. See No. 7 above
to determine whether you will be field cutting and swaging,
if you want the factory to cut the cables and swage on the
fittings, or if you will use swageless fittings.
When the fittings are swaged on at the
factory, some fittings are larger in diameter than the size
of the holes you want to drill in your intermediate members
(posts or cable braces). Our Push-Lock™ and Pull-Lock™
fittings are attached to the bare end of the cable after the
cable is passed through your intermediate members, so you
need to drill your intermediate post holes only large enough
for the cable to pass through, if you use that fitting. The
fittings illustrated below, however, require slightly larger
holes in your intermediate members for the fittings to pass
through.
 |
If the hardware is swaged on at the
factory and if the cable will pass through intermediate
posts or cable braces, one end of each cable should have one
of the following fittings.
The holes in your intermediate member
will be drilled for the diameter of the swaged fitting
passing through the intermediate member as shown in the
following illustrations:



Where the cable will not pass through any
intermediate members, you can order factory cut and swaged
cables using any hardware. You are not limited to the
fittings shown above.
If you will be using swageless fittings
or field swaging to attach to the cables, you need to drill
your intermediate post holes only large enough for the
cables to pass through the posts.
 |
Page 4
4/1/07
A print-friendly version is also available (PDF Format)
|
 |
|
If your cables will be cut and the
fittings swaged on at the factory, you will need to provide
the factory with measurements for your cable runs after the
posts have been installed. Contact the factory for
Measurement Worksheets required for factory cutting.
b) Mounting hardware on your end posts.
If you are mounting hardware on two sides of your corner
posts, then your corner posts are considered end posts for
this discussion.
You will need to put tensioners on at
least one end of each cable run. Following are tensioning
devices.


Note: With the Invisiware® Receiver or
Push-Lock™ tensioner, you will need up to 3-3/4” of space
between the back of your end post and any structure to
insert the fitting into the end post from the back side.


(Stair pitch elevation)
 |

The other end of each cable run can be
either a tensioner (above) or a non-tensioning device.
Following are non-tensioning devices.


Note: With the Radius Ferrule, Push-Lock™
or Pull-Lock™ fittings, you will need approximately 2-1/2”
of space between the back of your end post and any structure
to insert the fitting into the end post from the back side.


 |
Page 5
4/1/07 |
 |
|

c) How you wish to configure your corners
(if applicable).
See No. 2. Configuration of any corners
in your design above for ways to treat your corners.
The following illustrations demonstrate
how the hardware can be used on a single corner post. They
also illustrate how some hardware can be countersunk into
the post or mounted flush with the back of the post. Not all
combinations are shown here. If the hardware and cable run
all the way through the post in one direction, you will need
to use a hanger bolt end or hardware that is mounted to a
lag eye for the perpendicular direction, as shown in the
first six illustrations that follow.



|



 |
Page 6
4/1/07
A print-friendly version is also available (PDF Format)
|
 |
|
 |
d) Hardware used for stairs or severe
slopes.
You can use any of the fittings with a
fork or an eye in conjunction with a Lag Eye, to accommodate
stairs and slopes. These fittings are Adjust-A-Jaw® and
Adjust-A-Body® with Threaded Eye tensioners, and Ultra-tec®
Fixed Jaw and Push-Lock™ with threaded eye non-tensioning
fittings.
On pitches up to 35°, you can also use
No. R-6-62
Invisiware® Receivers on your 4x4 (3.5” square) end posts
without having to drill your holes at an angle.

Invisiware® Receivers are less expensive
than fittings with fork or eye ends and do not require lag
eyes and screws to mount them. When installed, they are
hidden inside the end post to help preserve that special
view. R-6-62 Invisiware® Receivers are especially designed
for 4x4 wood posts and can be an excellent choice for stairs
and slopes as well as straight runs.
Conclusion
Cable as a railing in-fill can be attractive, easy to
install and virtually maintenance free. Understanding the
above considerations when designing your cable railing will
go a long way toward insuring that code requirements are met
with a railing that you and your customer will be proud of.
|
Page 7
4/1/07
A print-friendly version is also available (PDF Format)
|
 |
|
|
|